Electrical Transformer Hot Seat

October 6th, 2010 Comments off

When Infrared Scanning electrical power distribution systems, including general purpose dry type transformers, MIDWEST frequently finds interesting, strange, and even dangerous situations that have nothing to do with Infrared Thermography.  Visualize a make shift rest area in a manufacturing plant. This area was next to the tool room.  There were two panel boards, some wire way with switches above it, and two small general purpose dry type transformers next to the panel boards. One transformer looked like an old 75 kva 480 volt to 208 volt transformer and the other looked like a new, maybe 25 kva general purpose transformer.  Both of the dry type transformers were very warm. On top of the large dry type transformer was a small microwave and a coffee maker.  On top of the small dry type transformer was a cushion.  This looked like a pretty comfortable kitchenette set up.

 

Anyone electrical should recognize the danger of coffee, liquid, around an open air, air cooled, general purpose dry type transformer. A liquid spill would seem inevitable.  Just a matter of time. Even if the transformer had weather shields, no one should ever be around it with liquid.

 

The smaller electrical power transformer was just a nice warm seat.  We have seen this a million times, especially in warehouse and other unheated or poorly heated manufacturing and industrial areas.  Usually the folks using these transformers as seat warmers are not electrical and have no idea of the danger below. 

 

A 75 kva 480 volt air cooled transformer can let out a horrific blast if the primary conductors short out. The transformer would become an instant hot seat and the arc blast from the open top vents could cause horrible burns to anyone nearby.  Add to this the shock hazard. An arcing fault could go to ground and some one touching the transformer could receive a deadly shock. Or something could easily be stuck into the vents and contact live conductors. We see these general purpose air cooled dry type transformers everywhere, and in sizes ranging from 5 kva to 500 kva.  When we see this danger, we politely let the person know the risk of shock or burn.  In a second, that nice warm seat could turn into a deadly hot seat. And that coffee pot stand could be the source of a deadly shock or horrible arcing burn, in a second.

Transformer Sampling Danger

May 21st, 2009 3 comments

MIDWEST is frequently asked if it is safe to take an oil sample from a sample valve under the secondary cables of a pad mount transformer while the transformer is still energized?  No, it is not safe. Do not do it.  We think it is extremely dangerous.  This is the location of possibly one of the most dangerous arc flash hazards in a facility.  You can’t wear enough PPE to protect yourself.  Keep away from the secondary.  Just opening the door to inspect it can be very dangerous.  In addition, you would be exposed to unsafe shock hazard.  Our recommendation is to sample the transformer during a scheduled outage.  We know very well in years past this was common practice for many service companies.  Those days are gone.  As they should be.