Archive

Posts Tagged ‘electrical transformer’

Electrical Transformer Voltage Taps Cause Open Circuit

July 21st, 2011 Comments off

MIDWEST Engineering got a call from a plant supervisor that bought a 225 kva general purpose dry type power transformer, 480 volts to 208 volts. They had installed the transformer and energized it. But they swore they got no voltage at the secondary, 208 volt, side. The transformer was tested by MIDWEST before it was shipped, including being energized at full voltage. In addition, an inductive load was put on the transformer as part of our final testing procedure. But they were certain their power transformer had failed because they had just a couple volts at the output when energized at 480 volts on the primary. And they said they didn’t do anything to the defective transformer. So we ended up shipping them a second unit and asked them to send the suspect transformer back. When the suspect transformer arrived, the switchgear shop checked it out and found no visual indications of failure. If an electrical power transformer fails such that there is no voltage on any secondary phases, we would expect to find the failure during a visual inspection. In a new or reconditioned electrical power transformer, during a three phase fault, a lot of energy must go somewhere and it is usually pretty obvious. In this case there was absolutely nothing visual to indicate a failure. Our first transformer test, turns ratio, helped us find the problem immediately. The buyer had changed the transformer taps, but they did not remove the varnish on the unused tap tabs sticking out the side of the transformer windings. Sometimes these tabs are totally insulated with varnish and it has to be cleaned off thoroughly before connecting the tap jumper. This case was a little bizarre because the bolts holding the jumpers did not make contact on the inside of any of the holes in the insulated tap tabs. Pretty strange to not have any contact at any of the three jumpers.  We have seen this problem before, but usually one or two of the tap jumpers makes some contact and a third is open.  When changing taps, one needs to clean the jumpers and the taps so as to make sure there is a good current carrying connection. A poor heating connection can do some real damage and may not be noticeable until it’s too late. So, in a way, they got lucky.

Power Transformer – Visible Defect at Top of Winding

April 22nd, 2011 1 comment
  
Power Transformers  Defect at Top of Winding

Power Transformers Defect at Top of Winding

MIDWEST frequently rejects equipment even thought it passes the electrical tests. Here’s an obvious example. MIDWEST’s Switchgear Shop rejected a 225 kva 480 volt delta to 480/277 volt wye dry type electrical transformer. We only had the core and coils, not the enclosure. The insulation resistance, winding resistance, and turns ration test results were all good. The transformer was energized at full primary voltage and had proper secondary voltage for the tap position. This all sounds good. So, why was the transformer classified scrap junk?  An inspection revealed the top two turns of the primary windings of one barrel had been crushed down. Something had been dropped onto these winding turns and pushed them down and separated them. The damage wasn’t physically dramatic. It was almost inconspicuous. But it was fatal to the transformer. In addition, this damage didn’t appear to have caused the fault that blew the fuses that resulted in the owner sending us the transformer to check it out. But we also found one of the ‘unused’ tap tabs was melted off to the point the bolt hole was completely gone. The end of the tab looked very clean. The transformer was connected in a different tap. On top of all this, the side of the winding seemed blackened by an apparent arc blast. Apparently the bolted connection at this tap became loose and the arcing completely destroyed the tap connection. The taps of the transformer were changed in an effort to restore power until a replacement transformer was installed. Sometimes the physical damage to electrical power transformers is very obvious. In this case, the damage to the electrical transformer was not as obvious as one might think.  At least until after it was found. Test results alone can not be used to evaluate the condition of electrical dry type power transformers. The transformer must also be thoroughly inspected. What MIDWEST calls a ‘hard focus’ inspection.

Replacement Transformer for One Too Hot to Touch

December 17th, 2010 Comments off

MIDWEST works a lot with electricians, maintenance mechanics, and other assorted electrical folks that have the every day job of keeping production machines running. When they call for help, for example when they suddenly need a replacement transformer, they want the short answer to their question. Sometimes you can tell from the edge in their voice that they are overwhelmed, in a real jam, and, if we put more burden on them by asking twenty questions about their old transformers, they are just going to stop listening, say thank you, and hang up. They want an immediate short answer to their immediate question.  This isn’t always possible or safe, but, since we have so much field service experience, we usually can get to the point quickly.

 

Sometimes the simplicity of the request can be amazing. For example, we had an electrician call during his lunch break and ask how he could tell if one of their old dry type transformers, used for production machines, was overheating. They had added a ton of equipment to it over recent years and he was worried the transformer was overloaded and would fail. His boss knew nothing about old, new, replacement electrical transformers and really didn’t want to be bothered with a “maybe problem.” The electrician needed something to get his bosses attention. He couldn’t measure the load, but he just knew it was overloaded.

 

Our unscientific suggestion was to put his hand on the top of the old power transformer enclosure. If he couldn’t hold it there for a few seconds, the transformer is in danger of being overloaded. The load should be measured and compared to the nameplate rating. If they don’t, they run the risk of the transformer failing when they least expect it, say the day before a holiday. Getting and installing a replacement transformer under emergency conditions can be a lot more expensive than scheduled transformer replacement. You don’t want to get burned.

 

Safety note. Be sure the transformer is grounded before touching it.

Electrical Transformer Hot Seat

October 6th, 2010 Comments off

When Infrared Scanning electrical power distribution systems, including general purpose dry type transformers, MIDWEST frequently finds interesting, strange, and even dangerous situations that have nothing to do with Infrared Thermography.  Visualize a make shift rest area in a manufacturing plant. This area was next to the tool room.  There were two panel boards, some wire way with switches above it, and two small general purpose dry type transformers next to the panel boards. One transformer looked like an old 75 kva 480 volt to 208 volt transformer and the other looked like a new, maybe 25 kva general purpose transformer.  Both of the dry type transformers were very warm. On top of the large dry type transformer was a small microwave and a coffee maker.  On top of the small dry type transformer was a cushion.  This looked like a pretty comfortable kitchenette set up.

 

Anyone electrical should recognize the danger of coffee, liquid, around an open air, air cooled, general purpose dry type transformer. A liquid spill would seem inevitable.  Just a matter of time. Even if the transformer had weather shields, no one should ever be around it with liquid.

 

The smaller electrical power transformer was just a nice warm seat.  We have seen this a million times, especially in warehouse and other unheated or poorly heated manufacturing and industrial areas.  Usually the folks using these transformers as seat warmers are not electrical and have no idea of the danger below. 

 

A 75 kva 480 volt air cooled transformer can let out a horrific blast if the primary conductors short out. The transformer would become an instant hot seat and the arc blast from the open top vents could cause horrible burns to anyone nearby.  Add to this the shock hazard. An arcing fault could go to ground and some one touching the transformer could receive a deadly shock. Or something could easily be stuck into the vents and contact live conductors. We see these general purpose air cooled dry type transformers everywhere, and in sizes ranging from 5 kva to 500 kva.  When we see this danger, we politely let the person know the risk of shock or burn.  In a second, that nice warm seat could turn into a deadly hot seat. And that coffee pot stand could be the source of a deadly shock or horrible arcing burn, in a second.